نموذج: SDP380D270J72000
| بيع الوحدات | : | Piece/Pieces |
The file is encrypted. Please fill in the following information to continue accessing it
|
Item |
Technical Requirements |
Unit |
Remarks |
|
|
Input Voltage Range |
380±10% |
Vac |
AC Input: 3-Phase, 4-Wire System |
|
|
Input Frequency |
50 Hz±10% |
Hz |
|
|
|
Maximum Input Current |
≤245 |
A |
(Full Load) |
|
|
Input Startup Delay |
3-10 |
S |
|
|
|
Overall Efficiency |
≥90 |
% |
Input Voltage: 380 VAC (Full Load) |
|
|
Power Factor (PF) |
≥0.9 |
/ |
Input Voltage: 380 VAC (Full Load) |
|
|
Output Power |
60kW |
12kW |
W |
|
|
Output Voltage |
270 |
28 |
V |
Dual Output |
|
Output Current |
220 |
428 |
A |
|
|
Voltage Regulation Accuracy |
≤±1% |
% |
|
|
|
Load Regulation |
≤±0.3% |
% |
|
|
|
Line Regulation |
≤±0.5% |
% |
|
|
|
Voltage Ripple & Noise |
≤350 |
mV |
@ 20 MHz Bandwidth |
|
|
Output Hold-up Time |
50 |
mS |
|
|
|
Input Overvoltage Protection |
≥430Vac |
V |
|
|
|
Input Undervoltage Protection |
< 325 Vac |
V |
|
|
|
Output Short-Circuit Protection |
Features short-circuit protection; automatically recovers once the short circuit is removed. |
/ |
|
|
|
Output Overcurrent Protection |
Yes |
/ |
|
|
|
Output Overvoltage Protection |
Yes |
/ |
|
|
|
Over-temperature Protection |
Yes |
/ |
Internal Chassis Ambient Temperature |
|
|
Operating Temperature |
-20_+50 |
℃ |
|
|
|
Storage Temperature |
-25_+70 |
℃ |
|
|
|
Withstand Voltage Test |
2.5 kVAC, 10 mA, 60 s — No arcing observed |
/ |
Input-Output and Chassis |
|
|
500 VDC, 10 mA, 60 s — No arcing observed |
/ |
Output-Chassis |
||
|
Insulation Resistance |
Insulation resistance: > 100 MΩ (at 500 VDC) |
/ |
Input-Output and Chassis |
|
|
Isolation Method |
Isolation |
/ |
Input-Output |
|
|
Cooling Method |
Forced air cooling |
/ |
|
|
|
Communication |
485 |
|
|
|
|
Unit Weight |
≤250 |
kg |
|
|
|
Dimensions (L×W×H)(mm) |
1600(L)*900(W)* 1200(H) |